The WFAR-TS T-tap water flow indicators shall be installed on a tee that has a 1 inch NPT branch include 1in.,11/4 in., 11/2 in. and 2in. as designated on the drawing and/or as specified herein. Water flow indicators shall mount on any clear pipe span of the appropriate normal size, either a horizontal or vertical pipe. The indicators shall have a sensitivity in the range of 4-10 gallons per minute and a static pressure rating up to 450psi for 1-2 (DN25 thru DN50) pipes. The indicator shall respond to water flow in the specified direction after a preset time delay that is field adjustable. The retard structure shall be a sealed mechanical pneumatic unit with visual time delay adjustment.
Rating Pressure:
|
Up to 450PSI (3.1MPa)
|
Flow Sensitivity:
|
4-10GPM (15.0-37.5L/min)
|
Maximum Surge:
|
18FPS (5.5m/s)
|
Contact Ratings:
|
Two sets of SPDT (Form C)
|
|
10.1Amps at 125/250 VAC
|
|
2.0Amps at 24 VDC
|
Enclosure Rating:
|
NEMA 4- suitable for indoor/outdoor use
|
Conduit Entrances:
|
Two opening for 1/2" conduit
|
|
One open, one knock-out type
|
Compatible Pipe:
|
Fits 1”, 1-1/4”,1-1/2” and 2” ferrous and brass threaded tees
|
Service Use:
|
Automatic Sprinkler: NFPA-13
|
|
One or Two Family Dwelling: NFPA-13D
|
|
Residential Occupancies up to 4 stories: NFPA-13R
|
|
National Fire Alarm Code: NFPA-72
|
Warranty:
|
3 Years
|